First, the fault phenomenon: the display meter indicates a negative value;
Possible cause: The display instrument is wrong with the pt100 thermal resistance wiring or the pt100 thermal resistance has a short circuit;
Treatment: Correct the wiring, or find the short circuit and strengthen the insulation.
Second, the failure phenomenon: the table of pt100 thermal resistance indicates infinity;
Possible causes: pt100 thermal resistance or lead wire short circuit or loose terminal block;
Treatment method: replace the resistor body or weld and tighten the terminal screws.
Third, the fault phenomenon: the indication value of the pt100 thermal resistance is lower than the actual value or the indication value is unstable;
Possible causes: metal chips, dust, dirt between the terminals and short circuit of the thermal resistance in the protection tube;
Treatment method: remove metal shavings, clean dust, water droplets, etc., find the short-circuit point to strengthen the insulation.
IV Symptom: PT100 thermal resistance value varies with temperature relationship;
Possible cause: corrosion and deterioration of silk material;
How to deal with it: Replace the pt100 thermal resistor .