The lightning protection system for UPS power and communication ports must be designed in accordance with national regulations, while also considering the specific conditions of the application environment. A practical and effective solution should be developed based on local requirements to establish a safe, scientific, and cost-effective lightning protection system. Given the characteristics of the UPS system, its lightning protection should focus on several key areas.
First, it's essential to enhance external lightning protection facilities and ensure proper grounding of the equipment room. According to the "Design Specification for Electronic Computer Room," a shared grounding system should be used for AC, DC working ground, protective ground, and lightning protection ground. The grounding resistance should meet the minimum required standards. If separate grounding is necessary, an equipotential coupling must be installed between the two locations. Since UPS systems are often part of large data systems, they are highly sensitive to lightning-induced surges. Even small potential differences can lead to significant damage or losses.
Multi-level lightning protection measures should be implemented. IEC61312-1 defines different lightning protection zones (LPZs), which help in structuring the protection strategy:
- **LPZOA (Open Area)**: Objects in this area may be directly struck by lightning, and the electromagnetic field from lightning can propagate freely without any attenuation.
- **LPZOB (Protected Area)**: Objects here are not directly struck by lightning but are still exposed to unshielded electromagnetic fields that can penetrate without reduction.
- **LPZ1**: This zone is inside a building and is protected from direct strikes. The current through conductors is lower than in LPZOB, and the electromagnetic field is reduced depending on the shielding measures in place.
- **LPZ2**: Further protection is introduced when additional reduction of lightning and electromagnetic fields is needed. The requirements for this zone depend on the specific needs of the protected system.
The core of lightning protection lies in **venting** and **equalization**. The surge protector should discharge as much of the lightning current as possible, directing it safely to the ground and preventing it from entering the communication system. For UPS systems with signal or communication interfaces, it's crucial to install a corresponding signal surge arrester at the interface to prevent lightning waves from being introduced via these lines.
The market for surge arresters is diverse, so it's important to choose reputable and reliable products. The grounding wire for the arrester should be at least 6mm² in cross-section, with the shortest and most direct connection possible. Using Kelvin wiring techniques can further reduce induced voltage on the leads.
Both the lightning protection box and the UPS power supply must be properly grounded. The surge protection device and the UPS should be connected through an equipotential bonding system. The UPS output circuit must have a dedicated ground wire. It's recommended to use high-quality grounding modules to ensure long-term reliability and corrosion resistance. These measures not only improve the performance of the grounding system but also reduce the need for frequent maintenance, saving costs over time.